| 382 | 9 | 94 |
| 下载次数 | 被引频次 | 阅读次数 |
对燃料电池备用电源进行了基站测试运行,包括在线式应用、离线式应用及长期稳定性测试,并依据氢气实际采购成本、氢气累计使用量、输出功率等,对燃料电池备用电源发电成本和发电效率进行了计算。测试结果表明:燃料电池备用电源可以基本满足通信基站应用要求,发电成本为6.96元/kWh,发电效率为43.1%。
Abstract:The fuel cell backup power system has been tested in a communication base station used as an online backup power supply and an offline emergency power supply.The experimental results show that,the fuel cell backup power system can automatically start up as soon as commercial power powers off to provide a continuous and stable power supply to the load of the base station,and it can charge the battery pack in the station at the same time.Based on the cost of hydrogen,accumulative consumption and output power,the power generation cost and efficiency of the fuel cell power system are evaluated during the long-term test.And the power generation cost is 6.96yuan/kWh,and the efficiency of the fuel cell power system is 43.1%.
[1]熊兰英.着力建设绿色电源,深入开展标准化研究[J].通信技术与标准,2008(10):2-4.
[2]衣宝廉.燃料电池——原理、技术、应用[M].北京:化学工业出版社,2003:5.
[3]Vasallo M J,Bravo J M,Andujar J M.Optimal sizing for UPS systems based on batteries and/or fuel cell[J].Applied Energy,2013,105:170-181.
[4]Zhan Y,Guo Y,Zhu J,et al.Intelligent power supply system with back-up fuel cell/battery hybrid power source[J].Journal of Power Sources,2008,179:745-753.
[5]Wang Y,Chen K S,Mishler J,et al.A review of polymer electrolyte membrane fuel cells:technology,applications,and needs on fundamental research[J].Applied Energy,2011,88:981-1007.
[6]Varkaraki E,Lymberopoulos N,Zachariou A.Hydrogen based emergency back-up system for telecommunication applications[J].Journal of Power Sources,2003,118:14-22.
[7]侯士彦,李然.氢燃料备用电源应用于通信领域的分析[J].电信科学,2012(9):81-89.
基本信息:
中图分类号:TM911.4
引用信息:
[1]刘常福,石伟玉,臧振明,等.燃料电池备用电源在通信基站的应用[J].电池工业,2013,18(Z2):110-114.